Cable tray is classified by the nec nfpa 70 the national electrical code as a support system and not as a raceway.
Type tc cable nec.
A common problem the update addresses is that fittings that pass the flexible cord listing requirements but not the tray cable listing requirements are being used with type tc tray cables nrtls list tray cable fittings and flexible cord fittings to the ul514b conduit tubing and cable fittings standard which requires different pulls test for the fittings used with flexible cord and the.
Once there click on their link to free access to the 2017 nec edition of nfpa 70.
340 6 underground feeder and branch circuit cable.
Generally speaking raceway completely encloses the cable inside of it.
Power and control tray cable type tc is a factory assembly of two or more insulated conductors under a nonmetallic jacket sec.
336 10 7 of the 2014 national electrical code nec and its corresponding exception is to make it clear that cable with only a tc rating cannot be run unprotected outside a raceway or cable tray.
Equipment grounding for the utilization equipment is provided by an equipment grounding conductor within the cable.
The national electric code nec defines tray cable as.
The intent of sec.
Type tc power and control tray cable is a factory assembly of two or more insulated conductors with or without associated bare or covered grounding conductors under a nonmetallic sheath approved for installation in cable trays in raceways or where supported by a messenger wire.
Type tc tray cable nec article 336 power and control tray cable type tc is a factory assembly of two or more insulated conductors with or without associated bare or covered grounding conductors under a non metallic jacket.
336 6 power and control tray cable.
See the actual nec text at nfpa org for the complete code section.
Types se and use.
Tc cables are rated for 600 volts and can be used in industrial power or control circuits where flame.
A factory assembly of two or more insulated conductors with or without associated bare or covered grounding conductors under a nonmetallic sheath for installation in cable trays in raceways or where supported by a messenger wire.
The cable that complies with the crush and impact requirements of type mc cable and is identified with the marking tc er the cable is secured at intervals not exceeding 1 8 m 6 ft.
Service entrance cable is a single or multiconductor assembly with or without an overall covering used primarily for services sec.
Ul stands for underwriter s laboratory and is an independent us testing organisation similar to the german vde.
It can be used when dropping out of cable tray to equipment or devices and also where dropping from tray to tray.